5. Install the Electrical Outlet - United States
WARNING: Risk of electric shock. Make sure the power has been disconnected before performing
the following procedures.
NOTE: For installations in Latin America, go to the Electrical Connections - Latin America section.
NOTICE: The control amplifier is equipped with a cord and plug. All wiring for the control amplifier has
been completed at the factory. A qualified electrician must install a GFCI- or RCD-protected, 120 V, 15 A
grounded outlet. No other load should be on this circuit.
Install a 120 V, 15 A grounded outlet within the wall framing and within 24 (610 mm) of the
planned control amplifier location. Route the wires through conduit for this outlet installation.
Control
Amplifier
120 V, 15 A
Grounded Outlet
24" (610 mm)
Maximum
Conduit
Ethernet Connector